NOTE: Power Pack only. Probe and Accessories sold Separately.
Call us on 1300 662 720 to get a quote on complete assembly.
The BinMaster PROCAP IX and IIX capacitance sensors feature CSA Class I, Groups C & D and Class II, Groups E, F, & G ratings. Suitable for challenging environments where there is a risk of explosion, they detect high or low levels in vessels used for volatile material storage. They function by detecting the presence or absence of material in contact with the probe by sensing minute changes (as low as 0.5 pF) in capacitance caused by the difference in the dielectric constant of the material versus the air. They feature interference-free operation, simple calibration, and fail-safe functionality and perform accurately even in dusty, sticky, or clinging materials. A vast assortment of probes and extensions make these point-level capacitance probes highly customizable for a variety of solid, liquid, and slurry materials.
Item Code | Description |
BC-PC1X. | PROCAP IX power pac with universal power supply 24 to 240 VAC/VDC with triple thread screw-off cover, dual conduit entries, DPDT relay contacts, selectable fail-safe protection, FDA recognized powder coat finish, hazardous location approved, C/US listed for Class I, Groups C & D and Class II, Groups E, F, G |
BC-PC2X. | PROCAP IIX power pac with selectable 115/230 VAC with triple thread screw-off cover, dual conduit entries, DPDT relay contacts, selectable fail-safe protection, FDA recognized powder coat finish, hazardous location approved, C/US listed for Class I, Groups C & D and Class II, Groups E, F, G |
PROCAP IX Power Requirements: Universal power supply 24 to 240 VAC/VDC
PROCAP IIX Power Requirements: Selectable 115/230 VAC
Output Relay: DPDT 10 Amp at 250 VAC
Ambient Temp: -40ยฐF to +185ยฐF (-40ยฐC to +85ยฐC)
Process Temp: To 250ยฐF Delrin probe (121ยฐC); to 500ยฐF Teflon probe (260ยฐC)
Pressure: 500 PSI Approvals & Certifications: Listed for Class I, Groups C & D and Class II, Groups E, F & G Hazardous Locations
Enclosure Type: NEMA 4X, 5, 7, 9 & 12
Housing Enclosure: Die cast aluminum, USDA approved powder coat finish
Mounting: 1-1/4โ NPT or 3/4โ NPT 316 SS standard; 1-1/4โ NPT 316 SS & sanitary flange optional
Diaphragm Switch for Hazardous Locations
Fail-Safe Rotary Level Indicator, features a comp…
3DLevelScanner for High Temperatures, has an oper…
Laser Level Transmitter, for level control, plugg…